Auckland Zoo Project

Requirement:

Wastewater from Auckland Zoo required treatment to remove e-coli and faecal coliforms to ensure safe compliant discharge back into the adjoining stream. An Envirolyte el-6000 Anolyte generator was installed to disinfect the wastewater prior to discharge.
The daily volume of water to treat is ~ 1,800 cubic metres. Concentration of Anolyte dosed is 0.27 % in Winter and 0.34 % in Summer producing a residual free available chlorine (FAC) level of around 1 ppm.

Outcome:

As shown in the test results table below the project has successfully treated the discharge contaminants to a safe level.

The Hippo pool water visibility is improved, staying cleaner for longer between flushing - a much healthier environment for "Snorkel" the Hippo to wallow in!

Location - Lower Hippo Enclosure
Pre Anolyte Treatment
Post Anolyte Treatment
Faecal Coliform Count (cfu/100ml)
1400 cfu/100 ml
< 2 cfu/100 ml
Escherichia Coli Count (cfu/100ml)
770 cfu/100 ml
< 2 cfu/100 ml



The technology: An Envirolyte EL-6000

Fully plumbed and wired in weatherproof building on concrete pad. Water softener unit, sediment filters, flowmeters, semi auto flushing kit, Anolyte, Catholyte and Salt storage tanks, and dosing system to waterway complete the installation.


To contact us:

Phone: 0274 972 440
Fax: 09 4321 240
Email: info@envirolyte.co.nz




Hippo Pond Before Dosing
Above, before treatment
Below, after Anolyte dosing commences
Envirolyte Technology Installation



Check this out? Living Heritage School Stories The children's view on the importance of maintaining an ecologically sensitive water supply throughout Auckland Zoo.



DEMM Engineering & Manufacturing Magazine
features an article about Snorkel the Hippo's home upgrade

© Copyright 2009 - Envirolyte NZ Ltd